(6) Reset to the factory default value(readable and writable)
Communication
address
Content
Data
length
0x0140
After writing data 0x1EA5 to this address, all parameters of
PA~PF and PL group will be reset to the default value, and the
writing will be completed after 3 seconds.
The setting range is 0~0xFFFF
When reading this parameter, if 1 is returned, it means the drive
is still writing EEPROM. If 0 is returned, it means the writing to
EEPROM is completed.
1word
(7)
Software input contact control(readable and writable)
Step 1: select the input mode of DI contact.
Communication
address
Content
Data
length
0x061E
Digital input source control option(PD16)
1. each bit of this parameter determines the signal input
control source of 1 DI.
Bit0 ~ Bit8 is correspond to DI1 ~ DI9
2.Bit setting shows as below:
0: input contact status is controlled by external hardware
terminal.
1: input contact status is controlled by communication
contact(PD25).
2word
Step 2: writing DI contact on/off status(ON/OFF)
Communication
address
Content
Setting
range
Data
length
0x0630
To write the status of DI (ON/OFF) as shown in below:
Writing data is valid only when the corresponding bit
of PD16 is 1, otherwise the actual DI contact status
will be still controlled by external hardware contact.
Refer to PD25 for details.
Refer to
PD16
2word
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit number
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...