31
3.3.2 CN1 signal wire shielding and grounding
The both ends of the CN1 signal wire which are the CN1 connector and the upper controller
connector, their shielding and grounding wire must be connected to the corresponding pins to
effectively achieve the shielding and grounding functions.
The shielding of CN1 encoder connector wiring instruction is as follows:
1. Pull out the metal shielding, surround and fix it with a copper sheet.
2.Screw the big metal case to fix the cooper sheet, make sure the copper sheet is completely
covered the extended metal sheet, and it is contact with the metal part of the CN1 connector.
3. Put it into the connector housing as below picture shows: