130
5.3.3 Auto tuning function
The auto-tuning function can estimate the load inertia ratio for servo drive in real time, and
automatically set the best gain (GAIN value) according to the estimated value and the
operation conditions. By using the auto-tuning function, the gain tuning of the servo drive can
be performed easily and quickly.
5.3.3.1Auto-tuning function
Auto-gain tuning mode 1
This mode is the factory default setting. If the servo is set to this function (PA02=0002), it will
estimate the load inertia ratio continuously and set the servo gain value automatically. The
only parameter that can be modified by the user is the response setting (PA03).
The related parameters and settings of this mode are as follows:
Parameter NO
Parameter
abbreviation
Parameter name
Modifiable
or
auto-estimated
PA03
ATUL
Auto-tuning response
level setting
Modifiable
PB06
GD1
Servo motor Load
inertia ratio
Auto-estimate
PB07
PG1
Position loop gain
Auto-estimate
PB08
VG1
Speed loop gain
Auto-estimate
PB09
VIC
Speed integral gain
Auto-estimate
The following conditions is required if you set the servo to auto-gain tuning mode 1.
1.The acceleration time from 0rpm to 2000rpm or the deceleration time from 2000rpm to
0rpm should be 2 seconds or less. If a 3000rpm case is applied, the acceleration and
deceleration time should be 3 seconds or less.
2.The speed command should be 250rpm or higher
3.The load inertia ratio should be 100 times or less.
4.This tuning mode is not applicable to those occasions with enormous load and inertia ratio
change.
5.Acceleration or deceleration torque should be the 10% or more of rated torque.
Auto gain tuning mode 2
When automatic gain tuning mode 1 cannot estimate the inertia correctly, you can use auto-
gain tuning mode 2. By setting PA02 to 0003 in this mode, the load inertia ratio will not be
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...