173
When performing the gain switching, the original servo gain value will be changed
to the ratio value (%)of PG2, VG2, and VIC.
Below are examples to illustrate the gain switching operation.
Example 1: digital input signal use as switching source.
①
.
Relevant parameters setting:
Name
Parameter
abbreviation
Parameter
code
Default
value
Unit
Servo motor load inertia
ratio
GD1
PB06
10
0.1time
Position loop gain
PG1
PB07
100
rad/s
Speed loop gain
VG1
PB08
500
rad/s
Speed integral gain
VIC
PB09
100
ms
Gain switching option
CDP
PB11
0001
N/A
Gain switching time
constant
CDT
PB13
10
ms
Servo motor load inertia
ratio 2
GD2
PB14
20
0.1times
Position loop gain change
ratio
PG2
PB15
80
%
Speed loop gain change
ratio
VG2
PB16
120
%
Speed integral gain
change ratio
VIC2
PB17
150
%
②
.
The gain switching diagram
Gain change
Gain value after switching
Gain value
before switching
Gain switching (CDP)
③
.
The states of parameters change
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...