6.3.6. Resonance suppression unit
(1)
Automatic high-frequency resonance suppression
Due to the limitation of the mechanism, Resonance may occur when the response
bandwidth of control system is too large, and this may cause damage on the mechanism.
Usually this phenomenon can be improved by increasing the rigidity of the mechanism or
reducing the bandwidth of the system, but it will increase the cost and reduce the response.
To suppress resonance without increasing the cost and reducing the bandwidth, this servo
drive provides Automatic High-frequency Resonance Suppression. its related parameters,
setting ranges and default values are shown in the below table. It mainly provides five groups
of resonance suppression filters and one group of low-pass filters to suppress resonance,
the user can manually or automatically operate as below instructions.
Name
Parameter
abbreviation
Parameter
code
Setting
range
Unit
Default
value
Control
mode
Auto resonance
suppression mode
ANCF
PB27
0~2
N/A
1
All
Auto-resonance
suppression
detection level
ANCL
PB28
1~300
%
50
All
Machine resonance
suppression
frequency 1
NHF1
PB01
10~4000
Hz
1000
All
Machine resonance
suppression
attenuation 1
NHD1
PB02
0~32
dB
0
All
Machine resonance
suppression
frequency 2
NHF2
PB21
10~4000
Hz
1000
All
Machine resonance
suppression
attenuation 2
NHD2
PB22
0~32
dB
0
All
Machine resonance
suppression
frequency 3
NHF3
PB25
10~4000
Hz
1000
All
Machine resonance
suppression
attenuation 3
NHD3
PB26
0~32
dB
0
All
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...