448
AL.32 Control circuit error 2
Alarm cause
Checking method
Corrective action
FPGA is abnormal.
Restart the drive. If the issue persists, send your
servo drive back to the distributor or
manufacturer.
AL.33
Memory error 2
Alarm cause
Checking method
Corrective action
Cache memory is abnormal.
Restart the drive. If the issue persists, send your
servo drive back to the distributor or
manufacturer.
AL.34
Over load 4
Alarm cause
Checking method
Corrective action
continuous use curve
which exceeds the
drive rated load.
Check if the frequency of the
repeatable operation cycle is
too fast.
Increase motor capacity or
reduce operation cycle
frequency.
Unstable system.
Check whether the
acceleration/deceleration time
setting is too short.
Increase the setting value of
acceleration/deceleration time.
AL.35 STO module abnormal
Alarm cause
Checking method
Corrective action
STO safety signal is
triggered.
Check if the STO safety
signal is triggered by CN6.
If CN6 is not used, check
whether the connector of
shipping configuration is
well connected.
Restart the drive after
checking. If the issue
persists, send your servo
drive back to the distributor
or manufacturer.
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...