HPV1000-App_Note_27
Closed Loop Start Guide
(Using the JVOP180 Keypad)
Guide to set up HPV1000 drive in Closed Loop Vf Control
Page 1: ...HPV1000 App_Note_27 HPV1000 App_Note_27 Closed Loop Start Guide Using the JVOP180 Keypad Guide to set up HPV1000 drive in Closed Loop Vf Control...
Page 2: ...erfaces it is recommended that the parameters in the drive be set to what is recommended by the elevator controller in their technical manual Closed Loop Operation Set up 1 Enter verify that the drive...
Page 3: ...Hoistway Parameter Set up 4 Enter verify the following parameters CONTRACT CAR SPD O1 25 parameter should be the lift contract speed in m s This can be verified with a hand tachometer if required and...
Page 4: ...has several options for autotuning the motor however usually the motor will be roped and so the Tune No Rotate1 Static method will be used If the ropes are off and the motor can turn freely the Standa...
Page 5: ...F1 05 between Forwards and Reverse Verify proper hoistway direction This can be reversed by changing both the MOTOR ROTATION B1 14 and ENCODER CONNECT F1 20 parameters Key Drive Parameters NOTE Key p...
Page 6: ...e while idle Can be monitored in the D2 menu PWM FREQUENCY C6 03 Carrier frequency 8 kHz Setting this parameter to 8kHz is a good starting value to ensure low motor noise Increasing this value will de...
Page 7: ...n Closed Loop Vect V f Control Open Loop Vector Closed Loop Vector PM ClosedLoop Vct Set to Closed Loop Vect Note not PM ClosedLoop Vct to run in Closed Loop mode Can be set to Open Loop Vect to run w...