7. PR (procedure) program control introductions
7.1
PR introduction
PR (Procedure) program: in the PR mode, the PR program is the smallest unit of the command.
It contains one or more programs and there are 64 groups of programs can be programmed.
They are a group of homing programs (PATH#0) and 63 groups of PR programs
(PATH#01~PATH#63). There are three different methods to trigger the program.
Standard trigger:
use POS1~POS6 to assign the triggering program, and triggered by
CTRG↑.
Event trigger:
the program is triggered by the rising or falling edge of EV1~EV4, and you can
refer to the parameters setting of PF83 and PF84.
Software trigger:
the program can be triggered by writing the required trigger number into
PF82 when servo is started.
7.2 The difference between the PR mode of SDP and SDA.
The PR mode of
SDA
The PR mode of SDP
Total number of
commands
8 independent
positions
1 set of homing (PATH#0)
63 sets of programs
(PATH#01~PATH#63)
Command type
positioning
command
positioning/speed/JUMP/WRITE/
Indexing positioning
Position command
Either absolute/
relative
Absolute/ incremental/relative(can use
alternatively)
Acceleration/deceleration
time
1 group
16 groups
Rotation speed
8 groups
16 groups
Delay time
N/A
16 groups
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...