450
AL.54 Motor parameter is out of range
Alarm cause
Checking method
Corrective action
When the motor executes the
PL02 motor parameter automatic
identification function, the motor
resistance (PL47) and inductance
(PL48) are out of range or are
zero, and then this alarm occurs.
Check if the motor
resistance (PL47),
inductance (PL48) values
are out of range or are
zero.
Check the value of
motor resistance
(PL47) and
inductance(PL48).
AL.55 Motor magnetic field error
Alarm cause
Checking method
Corrective action
1. The difference between
magnetic field feedback by the Hall
sensor and the control magnetic
field inside the servo is big.
2. Hall sensor three-phase (UVW)
are all high or all low and the
output time is over1ms.
1. Check whether the Hall
sensor is abnormal or
interfered.
2. Check whether there is
interference in the
feedback signal, which
caused pulses leakage.
Eliminate the Hall
sensor or feedback
signal problem, and
cycling the power.
AL.57 Feedback pulse is lost
Alarm cause
Checking method
Corrective action
Activate pulse lost detection, and
after initial Z phase signal output,
the pulse interval number between
every 2 Z phase output signal is
out of the range.
1.Check if the feedback is
normal.
2. Check if the pulse
interval number which
triggered by 2 Z phase
pulse is fixed value or not.
1.Eliminate
feedback abnormal.
2. Set correct pulse
number to PL39,
PL40.
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...