y=1: motor stops immediately when warning occurs
z: set the panel display status after alarm is
cleared.
z=0: the display stays in alarm screen after alarm is
cleared(AL--).
z=1: the display go back to the former screen after
alarm is cleared.
PC20
SNO
(*)
Servo drive communication device number
During communication different device number must
be set for different servo drives. If two drives are set
to the same device number, it will cause
communication failure.
All
1
1
~
32
Numb
er
PC21 CMS
(*)
Communication mode option
0 0 0 x
x: communication reply delay time(the parameter
change is valid only after power cycling)
x=0: reply within 0.5ms delay.
x=1: reply after 1ms delay.
x=2: reply after 2ms delay
All
0
0
~
2
N/A
PC22
BPS
(*)
Communication protocol option
0 0 y x
x: communication protocol option
x=0: 7,N,2 (Modbus, ASCII)
x=1: 7,E,1 (Modbus, ASCII)
x=2: 7,O,1 (Modbus, ASCII)
x=3: 8,N,2 (Modbus, ASCII)
x=4: 8,E,1 (Modbus, ASCII)
All 0010h
0000h
~
0058h
N/A