391
No.
Abbr.
Parameter function and description
Mode
Default
Range
Unit
The operation time is continuous operation time in
different load ratio. When the time exceeds the
level, AL.05 will occur. Below picture take load rate
200% as example.
If operate the motor base on the above operating
cycle, AL.05 will not occur.
PL21
Overload decrease gain:
Refer to PL20 for detail.
All
100
15 ~
600
%
PL22
Cogging compensation:
u z y x
x: Cogging Torque compensation function
1: enable
0: disable
y: estimate Cogging Torque
1: enable
0: disable
z: low-pass filter for estimation
1~A: 30~300 Hz
u: high-pass filter for estimation
1~A: 0.5~5K Hz
If PL22.yx = 11, Cogging data will be saved in
EEPROM, and then PL22.yx will switched to 01.
All 0x1A00
1100h
~
AA11h
N/A