194
Note 1: Es is the regenerated energy of a motor without loading that runs a rated speed then
stops.
The capacity of regenerative resistor is calculated as follows by using the Es and Ec in the
above table:
In which N: the Load inertia ratio T: operation cycle(Defined by user)
Assuming that the load inertia is N times the motor inertia, when the motor decelerates from
3000rpm to 0, the regenerative energy is (N+1)×Es and the regenerative resistor needs to
consume (N+1) × Es-Ec Joules. Assuming that the operation cycle is T sec, then the required
regenerative resistor power =2×((N+1) × Es
-
Ec) / T . the calculation is as follows
;
Note: J: motor inertia(unit:
kg
‧
m
2
), Wr: maximum speed of operation cycle(unit: rpm)
Step
Item
Calculation and instruction
1
Set the operation cycle T
Manual input(operation cycle)
2
Set rotation speed Wr
Manual input or read from panel status display(r)
3
Set load / motor inertia ratio N
Manual input or read from panel status display(Dc)
( PA01=0002 is valid)
4
Calculate the maximum
regenerative energy Es
Es = J * Wr
2
/ 182 ( if it’s rated speed, you can
check the value in the table directly)
5
Set the consumable
regenerative energy Ec
Refer to the above table
6
Calculate the capacity of
regenerative resistor
2 * ((N + 1) * Es - Ec) / T
Example 1
Taking the low inertia 400W model as an example, the operation cycle T = 1 sec, the
maximum speed is 3000rpm, and the load inertia is 20 times of the motor inertia, then the
required power of the regenerative resistor = 2 x ((20 + 1) x1.37 -9.9 ) / 1 = 37.7W. Therefore,
an external regenerative resistor above 37.7w is required.
Note: since the maximum speed of 3000rpm is rated speed of 400W motor, it can be found
from the above table that Es =1.37 J.
Example 2
Taking the middle inertia 2KW model as an example, the operation cycle T = 1 sec, the
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...