513
Please refer to the following wiring example for details.
Need
planning
Need
planning
13.2.2
Start procedure
(1)
Install absolute motor and battery.
(2)
Parameter setting.
PA28 is set to 1 which is absolute system setting.
Set PA34 to □□□0, and restart the drive to set the Delta absolute position detection
system.
And then restart again to activate the parameter setting.
(3)
[AL.2A Absolute encoder error 1] Alarm release.
When the battery is replaced and the power is turned on for the first time, an "AL.2A
Absolute Encoder error 1" alarm will occur. You can restart the power to release the
alarm.
(4)
Absolute position loss [AL.2C Absolute encoder error 3] Alarm release
When the absolute system is powered on for the first time, an alarm of "AL.2C Absolute
Encoder error 3" will occur. You can set PA29 to 1 or perform coordinate initialization to
clear the alarm.
(5)
Homing.
Origin setting should be done in the following conditions