424
0x0131
If “0x1EA5” is written to this address, it will clear all the alarm
record and occurrence time.
When reading this address, it will return the last alarm
record. The setting range is 0~0xFFFF.
1word
(5)Parameter reading and writing (readable and writable)
Communication
address
Content
Data
length
0x0300~0x03C5
PA group parameters, and the data length of each parameter
is 32 bits and occupying 2 addresses: such as PA01:
0x0300~0x0301.
2word
0x0400~0x04C5
PB group parameters, and the data length of each parameter
is 32 bits and occupying 2 addresses: such as PB01:
0x0400~0x0401.
2word
0x0500~0x05C5
PC group parameters, and the data length of each parameter
is 32 bits and occupying 2 addresses: such as PC01:
0x0500~0x0501.
2word
0x0600~0x06C5
PD group parameters, and the data length of each parameter
is 32 bits and occupying 2 addresses: such as PD01:
0x0600~0x0601.
2word
0x0700~0x07C5
PE group parameters, and the data length of each parameter
is 32 bits and occupying 2 addresses: such as PE01:
0x0700~0x0701.
2word
0x0800~0x08C5
PF group parameters, and the data length of each parameter
is 32 bits and occupying 2 addresses: such as PF01:
0x0800~0x0801.
2word
0x0A00~0x0A62
There are 99 parameters in PG group, and the data length of
each parameter is 16 bits.
1word
0x0B00~0x0B62
There are 99 parameters in PH group, and the data length of
each parameter is 16 bits.
1word
0x0E00~0x0EC5
PL group parameters, and the data length of each parameter
is 32 bits and occupying 2 addresses: such as PL01:
0x0E00~0x0E01.
2word
Note 1: the maximum allowance data in one access is 29 (29 words).
Note 2: when writing PA~PH group parameters by communication by using MODBUS 0x06 or
0x10 function code, the drive firmware must confirm that the write value cannot exceed the
range. If it exceeds the range and communication error will occur, you can refer to section 9.3
for details.
Summary of Contents for SDP Series
Page 33: ...20 400V series DC 24V Power supply Note terminal P N cannot be grounded ...
Page 45: ...32 4 The last step is to fasten the screw of housing ...
Page 385: ...372 ...
Page 405: ...392 ...
Page 499: ...486 SME L040 SME L075 SME L100 SME L150 ...
Page 500: ...487 SME L200 SME L300 SME M100 SME M150 ...
Page 509: ...496 When the load reaches 300 the operation time is 5 51 seconds ...
Page 555: ...542 14 5 Manual version and revision history Manual version V1 00 Release month July 2022 ...