background image

12 Digital Inputs

8 Digital Outputs

2 Analog Inputs

2 Analog Outputs (V)

2 Analog Outputs (I)

D20A6 expanded I/O

for AV-300i Drives

GE Industrial Systems

GE Industrial Systems

INSTRUCTIONS

Summary of Contents for D20A6

Page 1: ...12 Digital Inputs 8 Digital Outputs 2 Analog Inputs 2 Analog Outputs V 2 Analog Outputs I D20A6 expanded I O for AV 300i Drives GE Industrial Systems GE Industrial Systems INSTRUCTIONS ...

Page 2: ...ld be referred to GE Industrial Systems Salem Virginia USA This document contains proprietary information of General Electric Company USA and is furnished to its customer solely to assist that customer in the installation testing operation and or maintenance of the equipment described This document shall not be reproduced in whole or in part nor shall its contents be disclosed to any third party w...

Page 3: ...could be caused by the non observance of such indications depends on the different conditions Anyway the instructions given below should always be followed with the highest attention Attire l attention sur les modes d utilization et les procédés et conditions d exploitation qui en cas d inobservation pourraient entraîner la détérioration ou la destruction des appareils La gravité des blessures et ...

Page 4: ......

Page 5: ...NAL BOARD POINTS 15 3 2 DIGITAL OUTPUTS TERMINAL BOARD POINTS 15 3 3 ANALOG INPUTS TERMINAL BOARD POINTS 16 3 4 ANALOG OUTPUTS TERMINAL BOARD POINTS 16 3 5 FUNCTIONAL OVERVIEW 17 Chapter 4 JUMPERS 18 Chapter 5 LEDS 18 Chapter 6 TECHNICAL DATA 19 Dimensions and Weight 19 General Data 20 Digital Inputs 20 DigitalOutputs 20 Analog Inputs 20 Voltage Analog Outputs 21 Current Analog Outputs 21 Temperat...

Page 6: ...CInputpowersupplyisswitched on Minimumtimetowaitbeforeworkingontheterminalsorinternaldevices is listed in section 5 11 on Hardware Quick Start Up Guide If the front plate has to be removed because the ambient temperature is higher than 40 degrees the user has to ensure that no occasional contact with live parts will occur Always connect the Drive to the protective ground PE via the marked connecti...

Page 7: ...st supérieur à 3 5 mA Selon EN 50178 il faut prévoir dans ces cas une double connexion à terre WARNING ELECTRICAL SHOCK AND BURN HAZARD ATTENTION DÉCHARGE ÉLECTRIQUE ET RISQUE DE BRÚLURE When using instruments such as oscilloscopes to work on live equipment the oscilloscope s chassis should be grounded and a differential amplifier input should be used Care should be used in the selection of probes...

Page 8: ... use in industrial installations Parts of the Drives are at high voltage during operation The electrical installation and the opening of the device should therefore only be carried out by qualified personnel Improper installation of motors or Drives may therefore cause the failure of the device as well as serious injury to persons or material damage Follow the instructions given in this manual and...

Page 9: ...ds the allowable tempe rature Leave the ventilation cover attached for temperatures of 104 F 40 C or below If the Drive s Fault Alarm is activated consult the TROUBLESHOOTING section of Hardware Quick Start Up Guide and after correcting the problem resume operation Do not reset the alarm automatically by external sequence etc Be sure to remove the desicant dryer packet s when unpacking the Drive I...

Page 10: ...code Le raccordement devrait être fait par un connecteur certifié et mentionné à boucle fermé par les normes CSA et UL et dimensionné pour l épaisseur du cable correspondant Le connecteur doit être fixé a l aide d un instrument de serrage specifié par le producteur du connecteur Ne pas exécuter un test megger entre les bornes du drive ou entre les bornes du circuit de contrôle Étant donné que la t...

Page 11: ... rigidité diélectrique sur des parties du convertisseurs Pour mesurer les tensions des signaux il faut utiliser des instruments de mesure appropriés résistance interne minimale 10 kΩ V NOTE If the Drives have been stored for longer than three years the operation of the DC link capacitors may be impaired Before commissioning devices that have been stored for long periods connect them to a power sup...

Page 12: ...nalog inputs analog outputs to the drive It is possible to use only one I O expansion card per Drive This option card features 12optocoupled digital inputs 15V up to 30VDC 8 optocoupled digital outputs 15V up to 30VDC 2 analog inputs 10V or 0 up to20mA or 4 up to 20mA 2 analog outputs 10V 2 analog outputs 0 up to20mA or 4 up to 20mA Front side ...

Page 13: ...13 I O Expansion card D20A6 Back side ...

Page 14: ... expansion card 1 Switch the drive off 2 Fasten the D20A6 card to the drive regulation board by means of screws B and standoffs A 3 The D20A6 card is connected to the regulator card through the XH connector using the supplied connector The power supply 5V and the control signals are provided by the drive via the XH connector 4 Switch on the drive ...

Page 15: ...I9X DI10X DI11X GND n a not available expDA10 XDI1 XDI0 XDI0 DIGITAL INPUTS 3 2 DIGITAL OUTPUTS TERMINAL BOARD POINTS Digital outputs need a 15V 24V supply voltage The Drive TB can be used to supply 24VDC power AV 300i 24VDC supply maximum output 120 mA total including Encoder LAN EXP card and DGF or 350 mA without DGF Terminal 60 is power supply terminal 55 is the common power supply Connector Te...

Page 16: ...available expD30 ANALOG INPUTS XAI 3 4 ANALOG OUTPUTS TERMINAL BOARD POINTS Connector Terminal 11 12 13 14 15 Function Fw 1 X Analog output 3 GND Analog output 4 GND GND Function Fw 2 X An out 1X GND An out 2X GND GND Connector Terminal 21 22 23 24 25 Function Fw 1 X not available not available not available not available GND Function Fw 2 X An out 3X An out 3X An out 4X An out 4X GND expDA40 VOLT...

Page 17: ...PUTS 58 59 31 32 33 34 DIGITAL INPUTS CONNECTOR XDIO 35 GND 36 37 38 39 DIGITAL INPUTS CONNECTOR XDI1 40 DI4X DI5X DI6X DI7X GND DI8X DI9X DI10X DI11X GND DO6X DO7X Anal out 3 An out 1X Anal out 4 An out 2X An out 3X An out 3X An out 4X An out 4X An inp 1X An inp 1X An inp 2X An inp 2X Digital input 5 DI0X Digital input DI1X 6 7 Digital input DI2X Digital input DI3X 8 Digital output 3 DO0X Digital...

Page 18: ...0V 10V expDA50 S3 OFF OFF JUMPERS ON BOARD S2 I O available depending on drive firmware version Drive firmware 1 X from 2 X Digital Inputs 4 12 Digital Outputs 6 8 Analog Inputs 2 Analog Outputs 2 4 expDA75 Chapter 5 LEDs 5V ____________________ The led is lit when internal 5V power supply is available from the Drive 15V ___________________ The led is lit when 15V power supply is provided by the D...

Page 19: ...on card D20A6 Chapter 6 TECHNICAL DATA DimensionsandWeight 142 49 92 36 Dimensions _________________________________ 142 49mm 5 6 inches x 92 36 mm 3 63 inches Weight _____________________________________ 77 g 2 7 oz ...

Page 20: ...pin ULow _______ 3V Digital Outputs Output type _________________________________ open emitter Optocoupled Pull down __________________________________ 10 kΩ Outputs no _________________________________ 8 Connection _________________________________ common Ext supply External power supply ________________________ 15 up to 30VDC Output current ______________________________ 50mA max for any output ...

Page 21: ...alog Outputs Output type _________________________________ Current Outputs no _________________________________ 2 Max Output voltage __________________________ 0 up to 14V Output current ______________________________ 0 up to 20mA max 4 up to 20mA Bandwidth __________________________________ 2kHz Temperature Storage temperature _________________________ 20 70 C 68 158 F Operating temperature _____...

Page 22: ...Type PHOENIX CONTACT 5 contacts MC1 5 5 ST3 81 1803604 or equivalent Terminals XDQ __________________________ Type PHOENIX CONTACT 10 contacts MC 1 5 10 ST3 81 1803659 or equivalent Chapter 8 MAXIMUM WIRE SIZES Terminals on connector mm2 AWG XDQ XDI1 XDI2 XDI3 XAI XAQV XAQI 0 14 1 5 28 16 expDA80 ...

Page 23: ......

Page 24: ...1S5G21 GEI 100427A 001109 SIEI ...