Appendices
A - 158
AC Servomotors/Servo Drives 1S-series with Built-in EtherCAT® Communications User’s Manual (I586)
Event name
Capacitor Lifetime Warning
Event code
081C0000 hex
Meaning
The capacitor built into the Servo Drive reached the service life of the manufacturer’s guarantee.
Source
EtherCAT Master Function Mod-
ule
Source details
Slave
Detection
timing
Continuously
Error
attributes
Level
Observation
*1
*1. You can change the level to minor fault by using Warning Level Change 1 Selection (4020-05 hex).
Recovery
---
Log category
System log
Effects
User program
Continues.
Operation
Not affected.
Indicators
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
---
---
---
System
-defined
variables
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
The operating time of the capaci-
tor in the Servo Drive exceeded
the service life
Send the Servo Drive for repair or
replace the Servo Drive with a new
one. It is necessary to replace the
component that reached the ser-
vice life.
None
Attached
information
None
Precautions/
Remarks
AL status code: -, Error No.: A701 hex
Event name
Inrush Current Prevention Relay Lifetime Warning
Event code
081D0000 hex
Description
The inrush current prevention relay built into the Servo Drive reached the service life of the manufacturer's
guarantee.
Source
EtherCAT Master Function Mod-
ule
Source details
Slave
Detection
timing
Continuously
Error
attributes
Level
Observation
*1
*1. You can change the level to minor fault by using Warning Level Change 1 Selection (4020-05 hex).
Recovery
---
Log category
System log
Effects
User program
Continues.
Operation
Not affected.
Indicators
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
---
---
---
System
-defined
variables
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
The number of operating times of
the inrush current prevention
relay in the Servo Drive
exceeded the service life
Send the Servo Drive for repair or
replace the Servo Drive with a new
one. It is necessary to replace the
component that reached the ser-
vice life.
None
Attached
information
None
Precautions/
Remarks
AL status code: -, Error No.: A702 hex
Содержание R88D-1SN01H-ECT
Страница 17: ...15 CONTENTS AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586...
Страница 266: ...3 Specifications 3 102 AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586...
Страница 430: ...8 Safety Function 8 16 AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586...
Страница 568: ...10 Operation 10 10 AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586...
Страница 822: ...Appendices A 174 AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586...
Страница 823: ...AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586 I 1 I Index...
Страница 826: ...I 4 AC Servomotors Servo Drives 1S series with Built in EtherCAT Communications User s Manual I586 Appendices...
Страница 827: ......