Goodrive350-19 series VFD Function parameter list
- 272 -
Function
code
Name
Description
Default
value
Modify
the rotor.
P08.51
Current regulation
coefficient on
input side
This function code is used to adjust the current
display value on the AC input side.
0.00
–1.00
0.56
○
P08.52
STO lock
0: STO alarm lock
Alarm-lock means STO alarm must be reset after
state restoration when STO occurs.
1: STO alarm unlock
Alarm-unlock means when STO occurs, after state
restoration,
STO
alarm
will
disappear
automatically.
0
○
P08.53
Bias value of
upper limit
frequency of
torque control
0.00 Hz
–P00.03 (Max. output frequency)
Note:
This parameter is valid only for the torque
control mode.
0.00Hz
○
P08.54
Acceleration/dece
leration selection
of upper limit
frequency of
torque control
0: No limit on acceleration or deceleration
1: Acceleration/deceleration time 1
2: Acceleration/deceleration time 2
3: Acceleration/deceleration time 3
4: Acceleration/deceleration time 4
0
○
7.2.10 P09 PID control
Function
code
Name
Description
Default
value
Modify
P09.00
PID reference
source
When frequency command (P00.06, P00. 07) is
set to 7, or channel of voltage setup (P04.27) is set
to 6, the VFD running mode is process PID control.
This parameter determines the target reference
channel of process PID.
0: Keypad (P09.01)
0
○