Goodrive350-19 series VFD Function parameter list
- 374 -
Function
code
Name
Description
Default
value
Modify
judging pulse
threshold
(closed-loop)
input, the VFD runs with P92.08 at P92.09 and
detects the encoder pulse count. If the detected
encoder pulse count exceeds P92.11 within
P92.10, it is considered that braking force is
insufficient and slip risk may exist. Then the
multifunction output terminal outputs brake failure
signal and the brake slip fault and outputs the
brake failure fault (bE).
P92.08 setting range: 0.0%
–180.0% (of the motor
rated torque)
P92.09 setting range: 0.00Hz
–20.00Hz
P92.10 setting range: 0.0s
–30.0s
P92.11 setting range: 0
–20000
P92.12
Enabling
PT100/PT1000
temperature
detection
0x00
–0x11
Ones place: whether to enable PT100 temperature
detection
0: Disable
1: Enable
Tens
place:
whether
to
enable
PT1000
temperature detection
0: Disable
1: Enable
0x00
◎
P92.13
PT100
overtemperature
protection point
0.0
–150.0°C
120.0°C
○
P92.14
PT100
overtemperature
alarm point
0.0
–150.0°C
100.0°C
○
P92.15
PT100 calibration
temperature
upper limit
Temperature
sampling value
Temperature
P92.15
P92.16
P92.17
P92.18
To enable PT100 temperature detection, perform
120.0°C
○
P92.16
PT100 calibration
temperature lower
limit
10.0°C
○
P92.17
Digital of PT100
calibration upper
limit
2950
○