Goodrive350-19 series VFD Function parameter list
- 356 -
Function
code
Name
Description
Default
value
Modify
1: Same as jogging frequency
P90.18/P90.19
Brake status
Release
Close
P08.06
Output
frequency
Same as hoisting-oriented brake closing frequency
Same as jogging frequency
Close
Output
frequency
Brake status
Release
P90.37
Brake selection
for
forward/reverse
switchover
0
–1
0: Perform switchover without braking
1: Perform switchover with braking
When P90.37=0, the switchover is performed
directly, and the brake does not act.
Output
frequency
FWD/RVS
command
FWD
RVS
When P90.37=1, during the switchover, the VFD
decelerates with braking to stop, and then opens
the brake to run in reverse direction.
Output
frequency
FWD/RVS
command
FWD
RVS
P90.39
0
◎
P90.38
Restart selection
during braking
P90.38 setting range: 0
–1
0: No restart during braking
Running
command
Output
frequency
P 90.39
Wait time of
restart
FWD
REV
1: Restart allowed during braking
0
◎
P90.39
Wait time of
restart
0.5s
◎