Goodrive350-19 series VFD Commissioning
- 59 -
Table 5.3 Parameter settings for the closed-loop vector controlled winching application macro (using
analog reference -10V
–10V)
Function
code
Name
Setting
Remarks
P00.00
Speed control mode
3
Closed-loop vector control mode
P00.01
Command running
channel
1
Terminal
P00.06
Setting channel of A
frequency command
2
AI2
P00.07
Setting channel of B
frequency command
0
Keypad
P00.11
ACC time 1
10.0s
P00.12
DEC time 1
5.0s
P05.03
Function of S3 terminal
64
Upward position limit
P05.04
Function of S4 terminal
5
Fault reset
P05.29
Lower limit value of AI2
-10.00V
-10.00V
–P05.31
P05.30
Corresponding setting of
lower limit of AI2
100.0%
-300.0%
–300.0%
P05.31
Intermediate value 1 of
AI2
-0.10V
P05.29
–P05.33
P05.32
Corresponding setting of
intermediate value 1 of
AI2
0.0%
-300.0%
–300.0%
P05.33
Intermediate value 2 of
AI2
0.10V
P05.31
–P05.35
P05.34
Corresponding setting of
intermediate value 2 of
AI2
0.0%
-300.0%
–300.0%
P05.35
Upper limit value of AI2
10.00V
P05.33
–10.00V
P05.36
Corresponding setting of
upper limit of AI2
100.0%
-300.0%
–300.0%
P05.37
Input filter time of AI2
0.100s
0.000s
–10.000s
P05.38
HDIA high-speed pulse
input function
2
Input through the encoder
P05.44
HDIB high-speed pulse
input function
2
Input through the encoder
P06.03
RO1 output selection
49
Brake output
P06.04
RO2 output selection
5
VFD fault
P20.15
Speed measuring mode
1
Measuring the speed through HDIA