Goodrive350-19 series VFD STO function description
-530-
STO mode
STO trigger delay
1
and instruction delay
2
STO fault: STL1
Trigger delay < 10 ms
Instruction delay < 280 ms
STO fault: STL2
Trigger delay < 10 ms
Instruction delay < 280 ms
STO fault: STL3
Trigger delay < 10 ms
Instruction delay < 280 ms
STO fault: STO
Trigger delay < 10 ms
Instruction delay < 100 ms
1. STO trigger delay: Time interval between triggering the STO function and switching off the drive
output
2. STO instruction delay: Time interval between triggering the STO function and instructing STO
output status
E.3 STO function installation checklist
Before installing the STO function, check the items listed in the following table to ensure that the STO
function can be properly used.
Item
□
Ensure that the drive can be run or stopped randomly during commissioning.
□
Stop the drive (if it is running), disconnect the input power supply, and isolate the drive
from the power cable through the switch.
□
Check the STO circuit connection according to the circuit diagram.
□
Check whether the shield layer of the STO input cable is connected to the +24 V
reference ground COM.
□
Connect the power supply.
□
Test the STO function as follows after the motor stops running:
•
If the drive is running, send a stop command to it and wait until the shaft of the
motor stops rotating.
•
Activate the STO circuit and send a start command to the drive. Ensure that the
motor does not start.
•
Deactivate the STO circuit.
□
Restart the drive, and check whether the motor is running properly.
□
Test the STO function as follows when the motor is running: