Goodrive350-19 series VFD Operating
- 150 -
Sx
Sy
UP terminal
function selection=10
DOWN terminal
function selection=11
UP terminal state
DOWN terminal state
T
F
T
T
UP terminal frequency incremental integral speed P08.45
DOWN terminal frequency decremental integral speed P08.46
Related parameter list:
Function
code
Name
Description
Default
value
P00.03
Max. output frequency
P00.04
–400.00Hz
50.00Hz
P00.04
Upper limit of running
frequency
P00.05
–P00.03
50.00Hz
P00.05
Lower limit of running
frequency
0.00Hz
–P00.04
0.00Hz
P00.06
Setting channel of A
frequency command
0: Keypad
1: AI1
2: AI2
3: AI3
4: High speed pulse HDIA
5: Simple PLC program
6: Multi-step speed running
7: PID control
8: MODBUS communication
9: PROFIBUS/CANopen/DeviceNet
communication
10: Ethernet communication
11: High speed pulse HDIB
12: Pulse string AB
0
P00.07
Setting channel of B
frequency command
15