Goodrive350-19 series VFD Function parameter list
- 211 -
Function
code
Name
Description
Default
value
Modify
P01.15
Stop speed
0.00
–100.00Hz
0.50Hz
◎
P01.16
Stop speed
detection mode
0: Set value of speed (the only detection mode
valid in SVPWM mode)
1: Detection value of speed
0
◎
P01.17
Stop speed
detection time
0.00
–100.00s
0.50s
◎
P01.18
Running
protection of
power-on terminal
When the running command channel is controlled
by terminals, the system will detect running
terminal state automatically during power up.
0: Terminal running command is invalid during
power up. The VFD will not run during power up
even if the running command terminal is detected
to be valid, and the system is in running protection
state. The VFD will run only after this terminal is
cancelled and enabled again.
1: Terminal running command is valid during
power up. The system will start the VFD
automatically after initialization is done if the
running command terminal is detected to be valid
during power up.
2: During power on, the terminal-given running
command is invalid, and the POE fault is reported.
During power on, the VFD does not run but reports
the fault, although the running command terminal
is valid. The fault disappears only when the
running command is canceled.
Note: This function must be set with caution,
otherwise, serious consequences may occur.
0
○
P01.19
Action selection
when the running
frequency is
below lower limit
(lower limit should
This function code is used to set the running state
of VFD when the set frequency is below lower limit
frequency.
0: Run in lower limit of the frequency
0
◎