Goodrive350-19 series VFD Function parameter list
- 264 -
Function
code
Name
Description
Default
value
Modify
P08.04
Acceleration
time 4
Model
depended
○
P08.05
Deceleration
time 4
Model
depended
○
P08.06
Running
frequency of
jogging
This function code is used to define the reference
frequency of the VFD during jogging.
Setting range: 0.00Hz
–P00.03 (Max. output
frequency)
5.00Hz
○
P08.07
Acceleration time
of jogging
Jogging acceleration time is the time needed for
the VFD to accelerate from 0Hz to Max. output
frequency (P00.03).
Jogging deceleration time is the time needed from
decelerating from Max. output frequency (P00.03)
to 0Hz.
Setting range: 0.0
–3600.0s
Model
depended
○
P08.08
Deceleration time
of jogging
○
P08.09 Jump frequency 1 When the set frequency is within the range of jump
frequency, the VFD will run at the boundary of
jump frequency.
The VFD can avoid mechanical resonance point
by setting the jump frequency, and three jump
frequency points can be set. If the jump frequency
points are set to 0, this function will be invalid.
Set frequency f
Time t
Jump
frequency 2
1/2* jump amplitude 2
1/2* jump amplitude 2
Jump
frequency 1
1/2* jump amplitude 1
1/2* jump amplitude 1
Jump
frequency 3
1/2* jump amplitude 3
1/2* jump amplitude 3
Setting range: 0.00Hz
–P00.03 (Max. output
frequency)
0.00Hz
○
P08.10
Jump frequency
amplitude 1
0.00Hz
○
P08.11 Jump frequency 2
0.00Hz
○
P08.12
Jump frequency
amplitude 2
0.00Hz
○
P08.13 Jump frequency 3
0.00Hz
○
P08.14
Jump frequency
amplitude 3
0.00Hz
○