Goodrive350-19 series VFD Operating
- 187 -
,
Graded
reference
terminal 1
Graded
reference
terminal 2
Graded
reference
terminal 3
Graded
reference
terminal 4
Graded
reference
terminal 5
Speed
setting
Graded multi-step
speed reference 0
Function
code
OFF
P90.06
OFF
Graded multi-step
speed reference 1
Graded multi-step
speed reference 2
Graded multi-step
speed reference 3
Graded multi-step
speed reference 4
Graded multi-step
speed reference 5
OFF
P90.07
P90.08
P90.09
P90.10
P90.11
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
OFF
Related parameter list:
Function code
Name
Description
Default
value
P05.01
–P05.06
I/O extension
card
P25.01
–P25.08
Digital input function
selection
77: Graded reference terminal 1
78: Graded reference terminal 2
79: Graded reference terminal 3
80: Graded reference terminal 4
81: Graded reference terminal 5
P90.06
Graded multi-step speed
reference 0
-100.0
–100.0%, relative to
P00.03
0.0%
P90.07
Graded multi-step speed
reference 1
-100.0
–100.0%, relative to
P00.03
0.0%
P90.08
Graded multi-step speed
reference 2
-100.0
–100.0%, relative to
P00.03
0.0%
P90.09
Graded multi-step speed
reference 3
-100.0
–100.0%, relative to
P00.03
0.0%
P90.10
Graded multi-step speed
reference 4
-100.0
–100.0%, relative to
P00.03
0.0%
P90.11
Graded multi-step speed
reference 5
-100.0
–100.0%, relative to
P00.03
0.0%
Note:
The multi-step settings of a higher grade can be closed only after the multi-step settings of all
lower grades are closed.
6.5.16 Local encoder input
GD350-19 series VFD supports pulse count function by inputting the count pulse from HDI
high-speed pulse port. When the actual count value is no less than the set value, digital output