Goodrive350-19 series VFD Function parameter list
- 317 -
Function
code
Name
Description
Default
value
Modify
Note:
HDI height measuring is implemented
through the HDIA and HDIB and supports only
incremental 24V encoders.
P20.16
Frequency
division coefficient
0
–255
When this parameter is set to 0 or 1, frequency
division of 1:1 is implemented.
0
○
P20.17
Pulse filer
processing
0x0000
–0xffff
Bit0: Whether to enable encoder input filter
0: No filter
1: Filter
Bit1: Encoder signal filter mode (set Bit0 or Bit2 to
1)
0: Self-adaptive filter
1: Use P20.18 filter parameters
Bit2:
Whether
to
enable
encoder
frequency-division output filter
0: No filter
1: Filter
Bit3: Reserved
Bit4: Whether to enable pulse reference filter
0: No filter
1: Filter
Bit5: Pulse reference filter mode (valid when Bit4
is set to 1)
0: Self-adaptive filter
1: Use P20.19 filter parameters
Bit6: Frequency-divided output source setting
0: Encoder signals
1: Pulse reference signals
0x0033
○