Goodrive350-19 series VFD Optional peripheral accessories
-521-
VFD model
Input filter
Output filter
GD350-19-075G-6
GD350-19-090G-6
GD350-19-110G-6
FLT-P06200H-B
FLT-L06200H-B
GD350-19-132G-6
GD350-19-160G-6
GD350-19-185G-6
GD350-19-200G-6
FLT-P06300H-B
FLT-L06300H-B
GD350-19-220G-6
GD350-19-250G-6
GD350-19-280G-6
GD350-19-315G-6
FLT-P06400H-B
FLT-L06400H-B
GD350-19-355G-6
GD350-19-400G-6
FLT-P061000H-B
FLT-L061000H-B
GD350-19-450G-6
GD350-19-500G-6
GD350-19-560G-6
GD350-19-630G-6
Note:
The input EMI meets the C2 requirements after an input filter is configured.
The preceding table lists external accessories. You need to specify the ones you choose when
purchasing accessories.
D.9 Braking system
D.9.1 Braking component selection
When the VFD driving a high-inertia load decelerates or needs to decelerate abruptly, the motor runs
in the power generation state and transmits the load-carrying energy to the DC circuit of the VFD,
causing the bus voltage of the VFD to rise. If the bus voltage exceeds a specific value, the VFD
reports an overvoltage fault. To prevent this from happening, you need to configure braking
components.
The design, installation, commissioning, and operation of the device must
be performed by trained and qualified professionals.
Follow all the "Warning" instructions during the operation. Otherwise, major
physical injuries or property loss may be caused.