Goodrive350-19 series VFD Function parameter list
- 339 -
Function
code
Name
Description
Default
value
Modify
P25.27
S11 switch-off
delay
0.000s
○
P25.28
S12 terminal
switch-on delay
0.000s
○
P25.29
S12 switch-off
delay
0.000s
○
P25.30
Lower limit value
of AI3
These function codes define the relation between
analog input voltage and corresponding set value
of analog input. When the analog input voltage
exceeds the range of max./min. input, the max.
input or min. input will be adopted during
calculation.
When analog input is current input, 0
–20mA
current corresponds to 0
–10V voltage.
In different application cases, 100% of the analog
setting corresponds to different nominal values.
The figure below illustrates several settings.
-100%
100%
Corresponding
setting
AI
10V
20mA
0
AI3/AI4
Input filter time: Adjust the sensitivity of analog
input, increase this value properly can enhance
the anti-interference capacity of analog variables;
however, it will also degrade the sensitivity of
analog input.
Note:
AI3 can support 0
–10V/0–20mA input, when
AI3 selects 0
–20mA input, the corresponding
voltage of 20mA is 10V;
0.00V
○
P25.31
Corresponding
setting of lower
limit of AI3
0.0%
○
P25.32
Upper limit value
of AI3
10.00V
○
P25.33
Corresponding
setting of upper
limit of AI3
100.0%
○
P25.34
Input filter time of
AI3
0.030s
○