Goodrive350-19 series VFD Operating
- 124 -
Function
code
Name
Description
Default
value
P00.03 Max. output frequency P00.04
–400.00Hz
50.00Hz
P00.04
Upper limit of running
frequency
P00.05
–P00.03
50.00Hz
P00.05
Lower limit of running
frequency
0.00Hz
–P00.04
0.00Hz
P00.11
Acceleration time 1 0.0
–3600.0s
Model
depended
P00.12
Deceleration time 1 0.0
–3600.0s
Model
depended
P02.00
Type of motor 1
0: Asynchronous motor
1: Synchronous motor
0
P02.02
Rated power of
asynchronous motor 1
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
P02.04
Rated voltage of
asynchronous motor 1
0
–1200V
Model
depended
P04.00
V/F curve setting of
motor 1
0: Straight-type V/F curve
1: Multi-point V/F curve
2: Torque-down V/F curve (power 1.3)
3: Torque-down V/F curve (power 1.7)
4: Torque-down V/F curve (power 2.0)
5: Customized V/F (V/F separation)
0
P04.01
Torque boost of motor
1
0.0%: (automatic) 0.1%
–10.0%
0.0%
P04.02
Motor 1 torque boost
cut-off
0.0%
–50.0% (rated frequency of motor 1)
20.0%
P04.03
V/F frequency point 1
of motor 1
0.00Hz
–P04.05
0.00Hz