Goodrive350-19 series VFD Operating
- 130 -
Function
code
Name
Description
Default
value
P04.46
Current setting in I/F
mode for
asynchronous motor 2
When I/F control is adopted for asynchronous
motor 2, this parameter is used to set the output
current. The value is a percentage in relative to the
rated current of the motor.
Setting range: 0.0
–200.0%
120.0%
P04.47
Proportional
coefficient in I/F mode
for asynchronous
motor 2
When I/F control is adopted for asynchronous
motor 2, this parameter is used to set the
proportional coefficient of the output current
closed-loop control.
Setting range: 0
–5000
350
P04.48
Integral coefficient in
I/F mode for
asynchronous motor 2
When I/F control is adopted for asynchronous
motor 2, this parameter is used to set the integral
coefficient of the output current closed-loop control.
Setting range: 0
–5000
150
P04.49
Starting frequency for
switching off I/F mode
for asynchronous
motor 2
When I/F control is adopted for asynchronous
motor 2, this parameter is used to set the Starting
frequency for switching off the output current
closed-loop control. When the frequency is lower
than the value of this parameter, the current
closed-loop control in the I/F control mode is
enabled; and when the frequency is higher than
that, the current closed-loop control in the I/F
control mode is disabled.
Setting range: 0.00
–20.00 Hz
10.00Hz
P04.50
End frequency for
switching off I/F mode
for asynchronous
motor 1
P04.44
–P00.03
25.00Hz
P04.51
End frequency for
switching off I/F mode
for asynchronous
motor 2
P04.49
–P00.03
25.00Hz