Goodrive350-19 series VFD Operating
- 127 -
Function
code
Name
Description
Default
value
2: AI2
3: AI3
4: HDIA
5: Multi-step
6: PID
7: MODBUS communication
8: PROFIBUS/CANopen communication
9: Ethernet communication
10: HDIB
11: EtherCat/Profinet communication
12: PLC card
13: Reserved
P04.28
Set voltage value via
keypad
0.0%
–100.0% (rated motor voltage)
100.0%
P04.29 Voltage increase time 0.0
–3600.0s
5.0s
P04.30
Voltage decrease
time
0.0
–3600.0s
5.0s
P04.31
Output max. voltage P04.32
–100.0% (rated motor voltage)
100.0%
P04.32
Output min. voltage 0.0%
–P04.31 (rated motor voltage)
0.0%
P04.33
Flux-weakening
coefficient in the
constant power zone
1.00
–1.30
1.00
P04.34
Input current 1 in
synchronous motor
VF control
When the synchronous motor VF control mode is
enabled, this parameter is used to set the reactive
current of the motor when the output frequency is
lower than the frequency set in P04.36.
Setting range: -100.0%
–+100.0% (of the rated
current of the motor)
20.0%