Goodrive350-19 series VFD Function parameter list
- 212 -
Function
code
Name
Description
Default
value
Modify
be larger than 0) 1: Stop
2: Sleep
When the set frequency is below lower limit
frequency, the VFD coasts to stop; when the set
frequency is above lower limit again and continues
to be so after the time set by P01.20 elapses, the
VFD will be restored to running state automatically.
P01.20
Wake-up-from-sle
ep delay
This function code is used to set the sleep delay.
When the running frequency of VFD is below the
lower limit frequency, the VFD enters sleep state;
when the set frequency is above the lower limit
again and continues to be so after the time set by
P01.20 elapses, the VFD will run automatically.
Run
Sleep
t1
t2
Run
Time t
Output frequency f
t3=P01.20
t1
<
t2, the inverter does not run
t1+t2=t3, the inverter runs
t3
Setting range: 0.0
–3600.0s (valid when P.01.19 is
2)
0.0s
○
P01.21
Restart after
power cut
This function code sets the automatic running of
the VFD at next power-on after power down.
0: Disable restart
1: Enable restart, namely the VFD will run
automatically after the time set by P01.22 elapses
if the starting conditions are met.
0
○
P01.22
Waiting time of
restart after power
cut
This function code sets the waiting time before
automatically running at next power-on after power
down.
1.0s
○