Goodrive350-19 series VFD Function parameter list
- 369 -
Function
code
Name
Description
Default
value
Modify
P91.35
DEC position limit
restricted
frequency
0.00
–20.00Hz
10.00Hz
○
P91.36
Function selection
under set
frequency fault
0
–3
0: Invalid
1: When Set frequency before brake release <
Brake release frequency, the VFD reports A-SSF
alarm. When Set frequency after brake release <
Brake closing frequency, the VFD reports A-rSF,
the brake closes and the VFD runs at the set
frequency.
2: Set frequency before brake release < Brake
release frequency, the VFD reports A-SSF. When
Set frequency after brake release < Brake closing
frequency, the VFD reports A-rSF, the brake closes
and the VFD stops.
3: When Set frequency before brake release <
Brake release frequency, the VFD reports A-SSF.
When Set frequency after brake release < Brake
closing frequency, the VFD reports SFE fault.
2
◎
P91.37
Enabling tower
crane rotating
turbulence control
by HDO
0
–1
0: HDO keeps the same function as specified by
P06.00
1: HDO is used as PWM signal
P91.37=1: Enable the tower crane rotating
turbulence control. HDO connects to the PWM
input of the turbulence module. You can enable the
output voltage of the turbulence module to change
with the frequency by setting P91.38
–P91.47.
0
◎
P91.38 f0 frequency point
Duty cycle
Frequency
P91.39
P91.38
P91.40
P91.42
P91.44
P91.46
P91.41
P91.43
P91.45
P91.47
Duty cycle and multi-step frequency regulation are
used.
50.00Hz
○
P91.39
Duty cycle
corresponding to
f0 frequency point
100.0%
○
P91.40 f1 frequency point
40.00Hz
○
P91.41
Duty cycle
80.0%
○