Goodrive350-19 series VFD Function parameter list
- 202 -
correct factory password to enter the interface. (You are not advised to modify the factory
parameters. Incorrect parameter setting may cause operation exceptions or even damage to
the VFD.) When password protection does not take effect, you can change the password any
time. When P07.00 is set to 0, no user password is used. When P07.00 is set to a non-zero
value during VFD power-on, parameters are prevented from being modified by using the user
password function. When you modify function parameters through serial communication, the
user password protection function is also applicant and compliant with the same rule.
7.2.1 P00 Basic functions
Function
code
Name
Description
Default
value
Modify
P00.00
Speed control
mode
0: SVC 0
1: SVC 1
2: SVPWM
3: VC
Note:
If 0, 1 or 3 is selected, it is required to carry
out motor parameter autotuning first.
2
◎
P00.01
Running
command
channel
0: Keypad
1: Terminal
2: Communication
0
○
P00.02
Communication
running command
channel
0: MODBUS
1: PROFIBUS/CANopen/Devicenet
2: Ethernet
3: EtherCat/Profinet
4: PLC programmable card
5: Wireless communication card
Note:
1, 2, 3, 4 and 5 are extended functions
which are available only when corresponding
cards are used.
0
○
P00.03
Max. output
frequency
Used to set the maximum output frequency of the
VFD. It is the basis of frequency setup and the
acceleration/deceleration.
Setting range: Max. (P00.04, 10.00)
–150.00Hz
50.00Hz
◎
P00.04
Upper limit of
running frequency
The upper limit of running frequency is upper limit
value of VFD output frequency. This value cannot
be greater than the maximum output frequency.
50.00Hz
◎