Goodrive350-19 series VFD Operating
- 125 -
Function
code
Name
Description
Default
value
P04.04
V/F voltage point 1 of
motor 1
0.0%
–110.0%
0.0%
P04.05
V/F frequency point 2
of motor 1
P04.03
– P04.07
0.00Hz
P04.06
V/F voltage point 2 of
motor 1
0.0%
–110.0%
0.0%
P04.07
V/F frequency point 3
of motor 1
P04.05
–P02.02 or P04.05–P02.16
0.00Hz
P04.08
V/F voltage point 3 of
motor 1
0.0%
–110.0%
0.0%
P04.09
V/F slip compensation
gain of motor 1
0.0
–200.0%
100.0%
P04.10
Low-frequency
oscillation control
factor of motor 1
0
–100
10
P04.11
High-frequency
oscillation control
factor of motor 1
0
–100
10
P04.12
Oscillation control
threshold of motor 1
0.00Hz
–P00.03 (Max. output frequency)
30.00Hz
P04.13
V/F curve setup of
motor 2
0: Straight V/F curve;
1: Multi-point V/F curve
2: Torque-down V/F curve (1.3
th
order)
3: Torque-down V/F curve (1.7
th
order)
4: Torque-down V/F curve (2.0
th
order)
5: Customize V/F (V/F separation)
0
P04.14
Torque boost of motor
2
0.0%: (automatic) 0.1%
–10.0%
0.0%