Goodrive350-19 series VFD Function parameter list
- 296 -
Function
code
Name
Description
Default
value
Modify
P13.10
Reserved
variables
0.0
–359.9
0.0
○
P13.11
Maladjustment
detection time
This
parameter
is
used
to
adjust
the
responsiveness of anti-maladjustment function. If
the load inertia is large, increase the value of this
parameter properly, however, the responsiveness
may slow down accordingly.
Setting range: 0.0
–10.0s
0.5s
○
P13.12
High-frequency
compensation
coefficient of
synchronous
motor
This parameter is valid when the motor speed
exceeds the rated speed. If motor oscillation
occurred, adjust this parameter properly.
Setting range: 0.0
–100.0%
0.0
○
P13.13
High-frequency
injection current
0
–
300.0%
20.0%
◎
7.2.15 P14 Serial communication function
Function
code
Name
Description
Default
value
Modify
P14.00
Local
communication
address
Setting range: 1
–247
When the master is writing frames, and the slave
communication address is set to 0, it is the
broadcast communication address, and all the
slaves on the MODBUS bus will accept this frame,
but the slave never responds.
Local communication address is unique in the
communication network, which is the basis for
point-to-point communication between the upper
computer and the VFD.
Note: The slave address cannot be set to 0.
1
○
P14.01
Communication This parameter is used to set the data
4
○