Goodrive350-19 series VFD Function parameter list
- 263 -
Function
code
Name
Description
Default
value
Modify
P07.51
Output voltage of
the last but one
fault
0V
●
P07.52
Output current of
the last but one
fault
0.0A
●
P07.53
Bus voltage of the
last but one fault
0.0V
●
P07.54
Max. temperature
of the last but one
fault
-20.0
–120.0°C
0.0°C
●
P07.55
Input
terminal
state of the last
but one fault
0
●
P07.56
Output
terminal
state of the last
but one fault
0
●
7.2.9 P08 Enhanced functions
Function
code
Name
Description
Default
value
Modify
P08.00
Acceleration
time 2
See P00.11 and P00.12 for detailed definitions.
Goodrive350-19 series VFD defines four groups of
acceleration/deceleration time, which can be
selected by multi-function digital input terminal
(P05 group). The acceleration/deceleration time of
the VFD is the first group by default.
Setting range: 0.0
–3600.0s
Model
depended
○
P08.01
Deceleration
time 2
Model
depended
○
P08.02
Acceleration
time 3
Model
depended
○
P08.03
Deceleration
time 3
Model
depended
○