Goodrive350-19 series VFD Function parameter list
- 372 -
Function
code
Name
Description
Default
value
Modify
P92.02
Low-speed
running protection
time
Low-speed running protection is applied to devices
to which long-time low speed running is not
applicable, preventing overheating caused by late
dissipation.
Running
command
Low speed
protection
output
Output
frequency
(Hz)
Time (s)
P92.03
P92.02
When P92.02 is a non-zero value, low-speed
running protection is enabled, if the running
frequency of the VFD is equal to or less than
P92.03, and the last time is equal to or greater
than P92.02, the VFD reports a low-speed running
protection fault (LSP).
P92.02 setting range: 0.000
–50.000s
P92.03 setting range: 0.00
–20.00Hz
0.000s
◎
P92.03
Setting of
low-speed running
frequency
5.00Hz
○
P92.04
Overload
protection current
detection value
When P92.04>0, overload protection is enabled, if
the ramp frequency is equal to or greater than
(P90.16+2.00Hz) during upward running, the VFD
starts checking the current (closed-loop torque
current or open-closed output current). If the
current is equal to or greater than P92.04, the VFD
reports the overload protection alarm after the
detection time reaches P92.05. This restriction is
not applicable to downward running.
0.0%
◎
P92.05
Overload
detection time
0.5s
○