Goodrive350-19 series VFD Operating
- 118 -
Function
code
Name
Description
Default
value
4: Pulse frequency HDIA (the same as
above)
5: Multi-step speed (the same as above)
6: MODBUS communication (the same as
above)
7: PROFIBUS /CANopen/ DeviceNet
communication (the same as above)
8: Ethernet communication (the same as
above)
9: Pulse frequency HDIB (the same as
above)
10: EtherCat/Profinet communication
11: PLC
12: Reserved
Note:
For the options 1
–11, 100%
corresponds to the max. frequency.
P03.15
Source of upper limit
frequency setup of reverse
rotation in torque control
0: Keypad (P03.17)
1
–11: same as P03.14
0
P03.16
Keypad limit value of upper
limit frequency of forward
rotation in torque control
Value range: 0.00 Hz
–P00.03 (Max. output
frequency)
50.00Hz
P03.17
Keypad limit value of upper
limit frequency of reverse
rotation in torque control
50.00Hz
P03.18
Source of upper limit setup
of the torque when
motoring
0: Keypad (P03.20)
1: AI1 (100% relative to three times of
motor current)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as
0