Goodrive350-19 series VFD Function parameter list
- 235 -
Function
code
Name
Description
Default
value
Modify
motor 1
Setting range: 0
–5000
P04.43
Integral coefficient
in I/F mode for
asynchronous
motor 1
When I/F control is adopted for asynchronous
motor 1, this parameter is used to set the integral
coefficient of the output current closed-loop
control.
Setting range: 0
–5000
150
○
P04.44
Starting frequency
for switching off
I/F mode for
asynchronous
motor 1
When I/F control is adopted for asynchronous
motor 1, this parameter is used to set the starting
frequency for switching off the output current
closed-loop control. When the output frequency is
lower than the value of this parameter, the current
closed-loop control in the I/F control mode is
enabled; and when the output frequency is higher
than P04.50, the current closed-loop control in the
I/F control mode is disabled.
Output
frequency
Output
current
P04.44
P04.41/P
04.52
P04.50
Setting range: 0.00
–20.00 Hz
Note:
The frequency for completely switching off
the I/F control is a half of the motor rated
frequency.
10.00Hz
○
P04.45
Enabling I/F mode
for asynchronous
0: Disable
0
◎