Goodrive350-19 series VFD Function parameter list
- 232 -
Function
code
Name
Description
Default
value
Modify
1: Automatic energy-saving operation
Under light-load state, the motor can adjust the
output voltage automatically to achieve
energy-saving purpose
P04.27
Channel of
voltage setup
0: Keypad; output voltage is determined by P04.28
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step (the set value is determined by P10
group)
6: PID
7: MODBUS communication
8:
PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
10: HDIB
11: EtherCat/Profinet communication
12: PLC programmable card
13: Reserved
0
○
P04.28
Set voltage value
via keypad
When the channel for voltage setup is set to
"keypad", the value of this function code is digital
voltage set value.
Setting range: 0.0%
–100.0%
100.0%
○
P04.29
Voltage increase
time
Voltage increase time means the time needed
from outputting the min. voltage to accelerating to
output the max. voltage.
Voltage decrease time means the time needed
from outputting max. voltage to outputting the min.
voltage
5.0s
○
P04.30
Voltage decrease
time
5.0s
○