Goodrive350-19 series VFD Operating
- 160 -
Function
code
Name
Description
Default
value
29: C_AO2 from PLC (You need to set
P27.00 to 1.)
30: Running speed (relative to twice the
synchronous speed of motor)
31
–47: Reserved variable
P06.17
Lower limit of AO1 output
-300.0%
–P06.19
0.0%
P06.18
Corresponding AO1 output of
lower limit
0.00V
–10.00V
0.00V
P06.19
Upper limit of AO1 output
P06.17
–100.0%
100.0%
P06.20
Corresponding AO1 output of
upper limit
0.00V
–10.00V
10.00V
P06.21
AO1 output filter time
0.000s
–10.000s
0.000s
P06.22
–
P06.26
Reserved variable
0
–65535
0
P06.27
Lower limit of HDO output
-300.0%
–P06.29
0.0%
P06.28
Corresponding HDO output of
lower limit
0.00
–50.00kHz
0.0kHz
P06.29
Upper limit of HDO output
P06.27
–100.0%
100.0%
P06.30
Corresponding HDO output of
upper limit
0.00
–50.00kHz
50.00kHz
P06.31
HDO output filter time
0.000s
–10.000s
0.000s
6.5.11 Digital input
GD350-19 series VFD carries four programmable digital input terminals and two HDI input terminals.
The function of all the digital input terminals can be programmed by function codes. HDI input
terminal can be set to act as high-speed pulse input terminal or common digital input terminal; if it is
set to act as high-speed pulse input terminal, you can also set HDIA or HDIB high-speed pulse input
to serve as the frequency reference and encoder signal input.