Goodrive350-19 series VFD Operating
- 126 -
Function
code
Name
Description
Default
value
P04.15
Motor 2 torque boost
cut-off
0.0%
–50.0% (rated frequency of motor 1)
20.0%
P04.16
V/F frequency point 1
of motor 2
0.00Hz
–P04.18
0.00Hz
P04.17
V/F voltage point 1 of
motor 2
0.0%
–110.0%
0.0%
P04.18
V/F frequency point 2
of motor 2
P04.16
–P04.20
0.00Hz
P04.19
V/F voltage point 2 of
motor 2
0.0%
–110.0%
0.0%
P04.20
V/F frequency point 3
of motor 2
P04.18
–P02.02 or P04.18–P02.16
0.00Hz
P04.21
V/F voltage point 3 of
motor 2
0.0%
–110.0%
0.0%
P04.22
V/F slip compensation
gain of motor 2
0.0
–200.0%
100.0%
P04.23
Low-frequency
oscillation control
factor of motor 2
0
–100
10
P04.24
High-frequency
oscillation control
factor of motor 2
0
–100
10
P04.25
Oscillation control
threshold of motor 2
0.00Hz
–P00.03 (Max. output frequency)
30.00Hz
P04.26
Energy-saving run
0: No
1: Automatic energy-saving run
0
P04.27
Channel of voltage
setup
0: Keypad; output voltage is determined by P04.28
1: AI1
0