Goodrive350-19 series VFD Operating
- 149 -
0
1
2
3
4
5
6
7
8
9
10
11
Keypad
AI1
PROFIBUS\CANopen
MODBUS
PID
Multi-step speed
Simple PLC
HDI
AI3
AI2
Ethernet
UP/DOWN terminal
P08.44 tens setup
(frequency control
selection)
P17.14
Digital
adjustment
value of
keypad
P08.44 ones
(UP/DOWN terminal
control setting)
0
P00.03
1
A
frequency
command
(max. output
frequency)
0
UP/DOWN enable
0
Valid
Invalid
Valid
Invalid
Terminal function 12
Clear frequency
increase/decrease setup
Terminal function 33
Clear frequency
increase/decrease setup
temporarily
0
0
1
2
3
4
5
6
7
8
9
10
11
Keypad
AI1
PROFIBUS\CANopen
MODBUS
PID
Multi-step speed
Simple PLC
HDIA
AI3
AI2
Ethernet
P00.06
(A frequency command
selection)
P00.07
(B frequency command
selection)
P00.09
(combination mode of setup
source)
P00.05 (lower limit of running
frequency)
P17.00
Set
frequency
A
B
A+B
A-B
Max
(
A
,
B
)
Min
(
A
,
B
)
+
+
P17.02
Ramps reference
frequency
P00.08 (B frequency command reference
object selection)
Frequency set by keypad
0
1
2
3
4
5
P00.10
P00.10
Frequency set by keypad
P00.04 (upper limit of running
frequency)
Pulse string AB
HDIB
EtherCat/Profinet
PLC card
Pulse string AB
HDIB
EtherCat/Profinet
PLC card
GD350-19 VFD supports switch-over between different reference channels, and the rules for channel
switch-over are shown below.
Present reference
channel
P00.09
Multifunction terminal
function 13
Channel A switches to
channel B
Multifunction terminal
function 14
Combination setup
switches to channel A
Multifunction terminal
function 15
Combination setup
switches to channel B
A
B
/
/
B
A
/
/
A+B
/
A
B
A-B
/
A
B
Max (A, B)
/
A
B
Min (A, B)
/
A
B
Note: "/" indicates this multi-function terminal is invalid under present reference channel.
When setting the auxiliary frequency inside the VFD via multi-function terminal UP (10) and DOWN
(11), you can increase/decrease the frequency quickly by setting P08.45 (UP terminal frequency
incremental change rate) and P08.46 (DOWN terminal frequency decrement change rate).