Goodrive350-19 series VFD Function parameter list
- 270 -
Function
code
Name
Description
Default
value
Modify
P08.43 Reserved
0.01
–10.00
0.10s
○
P08.44
UP/DOWN
terminal control
setup
0x000
–0x221
Ones: Frequency control selection
0: UP/DOWN terminal setup is valid
1: UP/DOWN terminal setup is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: All frequency modes are valid
2: Invalid for multi-step speed when multi-step
speed takes priority
Hundreds: Action selection during stop
0: Valid
1: Valid during running, clear after stop
2: Valid during running, clear after receiving stop
command
0x000
○
P08.45
UP terminal
frequency
incremental
integral rate
0.01
–50.00Hz/s
0.50Hz/s
○
P08.46
DOWN terminal
frequency
decrement
change rate
0.01
–50.00Hz/s
0.50Hz/s
○
P08.47
Action selection
for frequency
setup during
power down
0x000
–0x111
Ones: Action selection for frequency setup (by
keypad digits) during power down
0: Save during power down
1: Zero out during power down
Tens: Action selection for frequency setup (by
MODBUS) during power down
0x000
○