Goodrive350-19 series VFD Operating
- 164 -
Setting
Function
Description
control and torque control
control mode, or vice versa.
30
Acceleration/deceleration
disabled
Ensure the VFD will not be impacted by external signals
(except for stop command), and maintains current output
frequency.
31
Counter trigger
Enable pulse counting of the counter.
33
Clear frequency
increase/decrease setting
temporarily
When the terminal is closed, the frequency value set by
UP/DOWN can be cleared to restore the reference
frequency to the frequency given by frequency command
channel; when terminal is disconnected, it will revert to
the frequency value after frequency increase/decrease
setting.
34
DC brake
The VFD starts DC brake immediately after the command
becomes valid.
35
Switching between motor 1
and motor 2
When this terminal is valid, you can realize switch-over
control of two motors.
36
Command switches to
keypad
When this terminal is valid, the running command
channel will switch to keypad compulsorily. If this function
becomes invalid, the running command channel will
revert to the original state.
37
Command switches to
terminal
When this terminal is valid, the running command
channel will switch to terminal compulsorily. If this
function becomes invalid, the running command channel
will revert to the original state.
38
Command switches to
communication
When this terminal is valid, the running command
channel will switch to communication compulsorily. If this
function becomes invalid, the running command channel
will revert to the original state.
39
Pre-exciting command
When this terminal is valid, motor pre-exciting will be
started until this terminal becomes invalid.
40
Clear power consumption
quantity
After this command becomes valid, the power
consumption quantity of the VFD will be zeroed out.