Goodrive350-19 series VFD Operating
- 113 -
Function
code
Name
Description
Default
value
P02.15
Rated power of
synchronous motor 1
0.1
–3000.0kW
Model
depended
P02.16
Rated frequency of
synchronous motor 1
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
P02.17
Number of pole pairs of
synchronous motor 1
1
–50
2
P02.18
Rated voltage of
synchronous motor 1
0
–1200V
Model
depended
P02.19
Rated current of
synchronous motor 1
0.8
–6000.0A
Model
depended
P05.01
–
P05.06
Function of multi-function
digital input terminal
(S1
–S4, HDIA, HDIB)
36: Command switches to keypad
37: Command switches to terminal
38: Command switches to communication
/
P07.01
Function parameter
copying
Range: 0
–4
0: No operation
1: Upload parameters to the keypad
2: Download all parameters (including motor
parameters)
3: Download non-motor parameters.
4: Download motor parameters.
0
P07.02
QUICK/JOG key function
Range: 0x00
–0x27
Ones: QUICK/JOG key function selection
0: No function
1: Jogging
2: Reserved
3: Switching between forward/reverse
rotation
4: Clear UP/DOWN setting
5: Coast to stop
0x01