Goodrive350-19 series VFD Commissioning
- 53 -
When the conical motor performs constant-power variable-frequency speed regulation (boost),
the max. rotational speed cannot exceed 1.2 times the rated speed (60Hz). Otherwise, the motor
cannot run properly since the pressure spring cannot be pushed due to the axial magnetic pull
force reduce, and therefore the VFD encounters the current limit or overcurrent fault.
5.6 Commissioning lifting in space voltage vector control
5.6.1 Wiring
(+)
PB
GD350-19 VFD
R
S
T
R
S
T
M
3~
U
V
W
PE
S1
S2
S3
S4
HDIA
HDIB
S5
COM
Brake
output
VFD fault
output
RO1A
RO1B
RO1C
RO2A
RO2B
RO2C
Lifting
Lowering
Graded reference terminal 1
Graded reference terminal 2
Graded reference terminal 3
Fault reset
Brake feedback
Braking resistor
PW
+24V
Figure 5.6 Wiring for lifting in space voltage vector control
Note:
If the wiring is performed according to Figure 5.2, most VFD parameters need no adjustment. If
the onsite function terminals are inconsistent with the terminals shown in the figure, adjust the input
and output terminal functions according to the actual wiring after selecting the space voltage vector
controlled lifting application macro.
5.6.2 Commissioning procedure
1. Check the wiring and ensure the wiring is proper.
2. Set P00.18=1 to restore to the factory settings.
3. Set P02 motor parameters.
4. Set P90.00=9 to select the space voltage vector controlled lifting function macro.
5. Perform low-speed trial running.