Goodrive350-19 series VFD Function parameter list
- 341 -
Function
code
Name
Description
Default
value
Modify
P26.19
Relay RO3
switch-on delay
Y electric level
Y valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
Setting range: 0.000
–50.000s
0.000s
○
P26.20
Relay RO3
switch-off delay
0.000s
○
P26.21
Relay RO4
switch-on delay
0.000s
○
P26.22
Relay RO4
switch-off delay
0.000s
○
P26.35
AO2 output
selection
Same as P06.14
0
○
P26.38
Lower limit of AO2
output
Above function codes define the relation between
output value and analog output. When the output
value exceeds the set max./min. output range, the
upper/low limit of output will be adopted during
calculation.
When analog output is current output, 1mA
corresponds to 0.5V voltage. In different
applications, 100% of output value corresponds to
different analog outputs.
10V (20mA)
0.0%
100.0%
AO
Setting range of P26.38: -300.0%
–P26.40
Setting range of P26.39: 0.00V
–10.00V
Setting range of P26.40: P26.38
–300.0%
Setting range of P26.41: 0.00V
–10.00V
Setting range of P26.42: 0.000s
–10.000s
0.0%
○
P26.39
Corresponding
AO2 output of
lower limit
0.00V
○
P26.40
Upper limit of AO2
output
100.0%
○
P26.41
Corresponding
AO2 output of
upper limit
10.00V
○
P26.42
AO2 output filter
time
0.000s
○