Goodrive350-19 series VFD Commissioning
- 86 -
5.11.3 Motor and macro switchover parameters
Function
code
Name
Description
Default
P08.31
Switchover between
motor 1 and motor 2
0x00
–0x14
Ones: Switchover channel
0: Terminal
1: MODBUS communication
2: PROFIBUS/CANopen/DeviceNet
communication
3: Ethernet communication
4: EtherCat/Profinet communication
Tens: Whether to allow switchover during
running
0: Disallow
1: Allow
0x00
P90.00
Hoisting function macro
setting
0
–12
0: Common application mode
1: Lifting mode 1 (in open-loop vector control)
2: Lifting mode 2 (in closed-loop vector control)
3: Horizontal moving mode (in space voltage
vector control)
4: Tower crane rotating mode
5: Conical motor application mode
6: User-defined function macro 1
7: User-defined function macro 2
8: User-defined function macro 3
9: Lifting mode 3 (in space voltage vector
control)
10: Construction hoist mode
11: Closed-loop winching (for lifting in mineral
wells and winches)
12: Open-loop winching (for lifting in mineral
wells and winches)
0
P90.01
Terminal-switched
function macro setting
0
–12
The switched function macro is determined by
P90.03.
0: Common application mode
0